Triple & Quad#
INSUL can model Triple and Quad panel constructions consisting of several layers, with a range of connections between panels, and with and without sound absorptive material in the air cavity.
To model a Triple panel construction:
-
Use the INSUL Panel tabs to select the Triple tab.

-
Update the setup across the Panel 1, Frame 1, Panel 2, Frame 2 and Panel 3 tabs to configure the INSUL model as required.
This can include modelling infill material in each cavity.
Prediction accuracy of Triple and Quad systems is different
Prediction accuracy seems to decrease as a function of the number of elements involved in the construction, and so for a Triple or Quad panel construction, the accuracy is appreciably less than for Single and Double panel constructions.
From the available data that we have to compare the results of INSUL predictions against laboratory tests, the accuracy (90% limits) is estimated to be 4 dB for the Rw or STC index for Triple systems.
For Quad systems, the accuracy tolerance is greater than 4 dB for the Rw or STC indices.
For STC ratings, the 8 dB rule can be important...
For some triple and quad panel constructions (e.g. masonry walls that have plasterboard linings on both sides) the STC rating is controlled entirely by the low-frequency dip in the transmission loss curve due to the 8 dB rule. The accuracy of the STC rating is then even less because you do not get the averaging effect across a number of frequencies normally associated with the Rw or STC rating method. The STC is completely determined by that single frequency with consequently only the lesser accuracy of a single band.